Select a category and enter your values below
Multiple conversions
To convert from Milliampere (mA) to Ampere (A), use the following formula:
Ampere (A)
= 11000× Milliampere (mA)
= 0.001× Milliampere (mA)
To convert from Milliampere (mA) to Microampere (μA), use the following formula:
Microampere (μA)
= 11000 × 106× Milliampere (mA)
= 1000× Milliampere (mA)
To convert from Milliampere (mA) to Kiloampere (kA), use the following formula:
Kiloampere (kA)
= 11000 × 11000× Milliampere (mA)
= 1106× Milliampere (mA)
= 10-6× Milliampere (mA)
To convert from Milliampere (mA) to Megaampere (MA), use the following formula:
Megaampere (MA)
= 11000 × 1106× Milliampere (mA)
= 1109× Milliampere (mA)
= 10-9× Milliampere (mA)
A milliampere (mA) is a crucial unit used to measure small amounts of electrical current.
Think of electrical current like the flow of water through a pipe. If a large pipe represents an ampere (A)—the standard unit for current—then a milliampere would be the tiny trickle of water flowing through a drinking straw.
It is part of the International System of Units (SI) and is equal to one-thousandth of an ampere.
1 A = 1,000 mA.
The milliampere is a standard submultiple of the ampere, the base unit for electrical current.
The prefix "milli" signifies one-thousandth (10-3).
This standardized measurement ensures that engineers, scientists, and technicians worldwide are using consistent values for measuring electricity.
Because a milliampere represents a very small amount of current, it is the perfect unit for measuring the power consumption of everyday small electronics.
You'll see mA used to describe the electricity needed for:
Electrical injury is governed by current through the body, not by voltage — which is why safety literature is written in milliamperes.
The commonly cited thresholds for a 50/60 Hz current passing hand-to-hand through an adult are:
The numbers explain a detail that often looks strange: a residual-current device (RCD or GFCI) trips at just 30 mA in Europe or 5 mA in North America. Those settings sit deliberately below the fibrillation range, not below the level at which a shock hurts. The device is not there to prevent a shock — it is there to cut the circuit before that shock becomes fatal.
Industrial instrumentation transmits measurements as a current between 4 and 20 mA rather than as a voltage, and the choice is deliberate.
Current is identical at every point in a series loop, so voltage drop along a long cable run — which would corrupt a voltage signal — has no effect on the reading. The live zero at 4 mA is equally purposeful: a healthy sensor reading its minimum still draws 4 mA, so a reading of 0 mA can only mean a broken wire or dead transmitter. A 0–20 mA scheme could not distinguish "minimum value" from "cable cut".